ProtectionIP65 when suitably mounted and terminated
Optical wavelength870nm
Maximum angular alignment±5°
Maximum angular displacement(static not auto-aligning)
Alarm sensitivity levels25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB))
AlarmObscuration drops to below pre-defined sensitivity level. Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds)
Alarm indicationApp Status - FIRE, Head Red Flashing LED, Alarm Relay Change Over (CO) Contact, Rating 2A @ 30 VDC
Test/Reset functionsBeam test function with App, Alarm latching / auto-reset selectable (default auto-reset), Alarm reset in latching mode with App reset function, removing power for > 5 seconds or momentarily apply > 5 VDC to reset connections in Beam Head
Fault sensitivity levellt;4%
MalfunctionsObscuration drops to below the fault sensitivity level within 1 second, Power Down or Supply Voltage < 9 VDC, Commissioning modes, Pre-Alignment and Auto-Alignment, Beam turned off during Beam Maintenance, Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
Fault indicationApp Status - FAULT, Head Yellow Flashing LED 1 Second, Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC
Normal ConditionObscuration level is above the Alarm sensitivity level, App Status - NORMAL, Programmable on/off, Head Green Flashing LED, Programmable on/off
Automatic alignment/compensationAuto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn't affect normal operating mode), Beam Contamination Compensation 4 hour monitoring. Compensation data available in the App
Manufacturer
Kita
Manufacturer code
PSFBBLUE
Weight
1.5 kg